FV-2148W Wall-Mount Voice Evacuation System

FV-2148W Wall-Mount Voice Evacuation System

FV-2148W Wall-Mount Voice Evacuation System

FV-2148W *AS Model*

FV-2148W is a compact and lightweight Voice Evacuation wall mount system. It is designed for both general and emergency purpose broadcasts. The wall mount system is comprised of the 4 pre-recorded Voice Evacuation messages, 480 W digital power amplifier modules, 10 speaker zone selector, and is able to connect up to 4 remote microphones. The FV-2148W can link with the fire alarm panel. Emergency messages are automatically broadcast when the fire alarm is activated.
An optional MP-300 module is available for playback of background music to the speaker.

0dB = 1 V
Model FV-2148W
Power Source 100 - 240 V AC ~ 50/60 Hz, M4 screw terminal
Power Consumption 99 W (EN 62368-1)
530 W (Rated Output)
Rated Output 480 W
Input Front Microphone: -60 dB*, 2.2 KΩ, unbalanced, XLR connector 
Input 1: -60 dB*/-20dB* (selectable), 2.2 KΩ, balanced, screw terminal 
phone jack priority (if connected to phone jack, voice changes automatically) 
Input 2: -20 dB*, 10 KΩ, balanced, screw terminal
Remote Microphone Usable remote microphone: RM-200M Max 4 unit, RJ45 Maximum Cable Distance: Total 800m
Output Speaker output: Screw terminal 
Speaker Selector: 10 zones, high impedance (100V line) individual selector, group
S/N Ratio  Over 60 dB 
Total Harmonic Distortion  Under 1 % at 1 kHz, 1 /3 rated power 
Frequency Response  50 Hz - 20000 Hz 
Tone Control  Bass: ± 10 dB at 100 Hz Treble: ± 10 dB at 10 kHz 
Emergency Announcement  Alert, Evacuation, False, Clear
(repeated continuously / one time, selectable)
Built-in Chime  2 chimes 
Control Input  FA IN: No-voltage make contact input, open voltage: 24 V DC, short-circuit current: under 5mA, screw terminal 
CTRL IN 1 - 6: No-voltage make contact input, open voltage: 24 V DC, short-circuit current: under 5mA, screw terminal. (assignable)
Control Output  FA OUT: Relay contact output, rated voltage: 24 V DC, screw terminal
CTRL OUT 1 - 2: Relay contact output, rated voltage: 24 V DC, screw terminal (assignable)
Indicator  Power, Signal, Peak, Fault
Each of Zone, All Zone
Alert, Evacuation, False, Clear 
Operating Temperature 0 ·c to +40 ·c
Operating Humidity  Under 90 % RH (no condensation) 
Ventilation  Fan Cooling 
Finish Steel Plate, Painting, Black 
Dimensions  370 (W) x 456 (H) x 132 (D) mm 
Weight 9.1 kg
Accessories Front Microphone, Paper pattern
Optional  MP-300

Option to include the MP3 player MP-300
MP-300